8/16/24/32 Channel Data Acquisition System (VPL-DAS)
The VPL-DAS is a powerful Data Acquisition System specially designed for VPL’s series of Data Acquisition Modules. The System consists the following modules:
8~32-Channel Thermocouple Input (I-7018)
- Analog Input Channels: 8~32 differential
- Analog Input type: mV, V, mA
- Thermocouple type: J, K, T, E, R, S, B, N, C
- Voltage range: ±15mV, ±50mV, ±100mV, ±500mV, ±1V, ±2.5V
- Current range: ±20mA
- Sampling Rate: 10 samples/sec
- Bandwidth: 15.7Hz
- Accuracy: ±0.2%
- Zero drift: 0.5μV/°C
- Span drift: 25ppm/°C
- CMR @ 50/60Hz: 150dB min
- NMR @ 50/60Hz: 100dB min
- Input impedance: 20Mohm
- Voltage overload protection: ±35V
- Isolation: 3000V DC
- Communication Interface: RS485
- Power requirement: +10 to +30V DC
- Power consumption: 1.0W
RS-232 to RS-485 Protocol Converter (I-7520)
- Input : RS-232 protocol
- Output : RS-485 protocol
- “Self Tuner” inside
- Speed : 300 ~ 115,200 bps
- 256 modules in one RS-485 network without Repeater
- 3000 V isolation
- Multiple Baud Rate
- Multiple Data Format
Digital I/O Module (I-7050)
- Digital input channels: 7
- Level : TTL Logic Level 0: +1V max. Logic Level 1: 3.5V~+30V
- Digital output channels: 8 Open collector to 30V, 30mA max. load Power dissipation: 300mW
- Input frequency: 100Hz
- Safe value (when Host fail or communication fail)
- Power on preset value
- Dual Watchdog Timer
EZ DATA LOGGER SOFTWARE
It is a small data logger software. It can be applied to small remote I/O system. With its user-friendly interface, users can quickly and easily build a data logger software without any programming skill.
Features:
- Support DCON, Modbus RTU, Modbus Ascii, Modbus TCP(support IP and Domain name) protocols, mutiple COM Ports and TCP/IP connections, Virtual Channel definition, Control Logic (VB Script), Alarm Notifier (by sending SMS or E-Mail)
- Flexible module configuration, workgroup configuration
- Real time data trend (with zoom in and zoom out)
- Layout view
- IP Camera Viewer
- Access database supported
- Reporter
- High/Low alarm with audio warning
- Can search for DCON modules and M7000 serial modules
- Value scaling
- Support 3 level account
- Programming skill needless
ORDERING INFORMATION
- VPL-DAS-1: 8 Channel Data Logger
- VPL-DAS-2: 16 Channel Data Logger
- VPL-DAS-3: 24 Channel Data Logger
- VPL-DAS-4: 32 Channel Data Logger
Note: Specifications can be changed, added or subtracted without notice in our constant efforts for improvement.